Análise e validação dos sistemas de monitoramento de transformadores de extra alta tensão - um estudo de caso

dc.contributor.advisorSilva e Melo, Victor Alves
dc.contributor.authorSantos, Leonardo Francelino dos
dc.contributor.refereeFerreira, Reginaldo Vagner
dc.contributor.refereeCosta e Silva, Paulo Roberto
dc.date.accessioned2026-07-16T03:14:41Z
dc.date.created2026-02-13
dc.descriptionO monitoramento de transformadores de extra alta tensão é essencial para assegurar a confiabilidade do sistema elétrico e prevenir falhas de grande impacto operacional. Este trabalho apresenta uma análise comparativa entre dois transformadores submetidos a condições reais de anomalia, avaliando a eficácia dos sensores intrínsecos, das proteções mecânicas e do relé multifunção SEL-2414 da Schweitzer na prevenção de danos severos. A metodologia envolveu revisão bibliográfica, levantamento documental, análise de registros de relé, inspeções de campo e comparação direta entre um transformador que evoluiu para incêndio e outro preservado pela atuação imediata das proteções. Os resultados mostram que, no caso em que houve perda total do equipamento, a falta permaneceu sustentada por vários minutos devido à atuação tardia dos dispositivos e à insuficiência da lógica de correlação entre as variáveis monitoradas. Em contraste, o transformador preservado teve desligamento em frações de segundo, evitando elevação térmica, formação de gases e danos estruturais. Constatou-se que a eficácia do monitoramento depende diretamente da correta parametrização, da integração entre sensores e da velocidade de resposta do sistema de proteção. Conclui-se que arquiteturas de supervisão bem configuradas ampliam a disponibilidade dos equipamentos, reduzem riscos operacionais e contribuem para práticas de manutenção preventiva e preditiva mais assertivas.
dc.description.abstractMonitoring extra‑high‑voltage transformers is essential to ensuring the reliability of the electrical system and preventing failures with significant operational impact. This study presents a comparative analysis between two transformers subjected to real anomaly conditions, evaluating the effectiveness of intrinsic sensors, mechanical protections, and the Schweitzer SEL‑2414 multifunction relay in preventing severe damage. The methodology included a literature review, document analysis, relay record examination, field inspections, and direct comparison between one transformer that evolved into a fire and another that was preserved through the immediate action of protection devices. The results show that, in the case where the equipment suffered total loss, the fault remained sustained for several minutes due to delayed operation of the devices and insufficient correlation logic among monitored variables. In contrast, the preserved transformer was disconnected within fractions of a second, preventing thermal rise, gas formation, and structural damage. It was found that the effectiveness of monitoring depends directly on proper parameter configuration, integration among sensors, and the response speed of the protection system. It is concluded that well‑configured supervision architectures increase equipment availability, reduce operational risks, and contribute to more accurate preventive and predictive maintenance practices.
dc.identifier.advisorOrcid0009-0004-2075-8457
dc.identifier.authorOrcid0009-0003-8453-1502
dc.identifier.urihttp://hdl.handle.net/20.500.14387/3307
dc.language.isopor
dc.publisher.campiBetim
dc.publisher.countryBrasil
dc.publisher.institutionInstituto Federal de Minas Gerais
dc.publisher.programBacharelado em Engenharia de Controle e Automação
dc.rightsAcesso aberto
dc.subject.cnpqEngenharias
dc.subject.keywordsTransformador
dc.subject.keywordsMonitoramento
dc.subject.keywordsManutenção preventiva
dc.titleAnálise e validação dos sistemas de monitoramento de transformadores de extra alta tensão - um estudo de caso
dc.title.alternativeAnalysis and validation of extra-high-voltage transformer monitoring systems – a case study
dc.typeTrabalho de Conclusão de Curso

Arquivos

Pacote original

Agora exibindo 1 - 1 de 1
Carregando...
Imagem de Miniatura
Nome:
TCC - LEONARDO FRANCELINO DOS SANTOS FINAL.pdf
Tamanho:
2.49 MB
Formato:
Adobe Portable Document Format

Licença do pacote

Agora exibindo 1 - 1 de 1
Carregando...
Imagem de Miniatura
Nome:
license.txt
Tamanho:
1.72 KB
Formato:
Item-specific license agreed to upon submission
Descrição: